TG38-12 series Indoor AC high voltage isolation switch

Short Description:


  • Port: tianjing
  • Supply Ability: TENPRO
  • Payment Terms: L/C,D/A,D/P,T/T
  • Product Detail

    Product characteristics

    ·Small size and low cost

    ·Easy to operate

    ·High mechanical life

    ·Self-contained sensors and monitors

    ·Low environmental requirements

    ·Optional front and wall-mounted operation

    TG38-12 series

    Indoor AC high voltage isolation switch

    Outline

    TG38-12KV Series indoor AC high voltage isolation switch is a kind of isolation switch with obvious safety fracture, which is designed and developed by our company according to GB1985-2004 High Voltage AC Isolation Switch and Grounding Switch. The isolation switch has the advantages of small volume, simple and reasonable structure, small operation and closing force of spring mechanism, reliable performance and convenient maintenance, etc. It is used in unit with 12KV high voltage fixed circuit breaker and PT, CT. It is a high-cost isolating switch with superior cost performance

    Model description
    xdf

    Note: The insulator of the switch can be optionally equipped with a sensor with a live display.

    Main technical parameters

    Serial No.

    Item

    Unit

    Isolation switch

    1

    rated voltage

    kV

    12

    2

    rated current

    A

    630;1250

    3

    rated frequency

    Hz

    50

    4

    rated peak withstand current

    kA

    63

    5

    rated short-time withstand current (4 seconds)

    kA

    25

    6

    1min power frequency tolerance voltage (RMS) to ground, interphase / isolated fracture

    KV/KV

    42/48

    7

    Full wave lightning impulse withstand voltage (peak) to ground, interphase / isolated fracture

    KV/KV

    75/85

    8

    Main loop resistance

    μΩ

    ≤50,≤35

    9

    Interphase center distance

    mm

    210±3 OR185±3

    10

    Isolation knife opening distance

    mm

    ≥125

    11

    Manual maximum operating torque

    N·m

    ≤100

    Use environment condition

    1. Altitude ≤ 1000m;
    2. Ambient temperature -25 ℃ ~ 40 ℃;
    3. The daily average value of relative humidity is not greater than 95%   and the monthly average value is not more than 90%;
    4. Ambient air should not be corrosive or flammable gas, water vapor and other obvious pollution;
    5. Places free from fire and explosion hazards;
    6. A place with the earthquake intensity does not exceed 8 degrees; the slope does not exceed 5 °

     

     